Input | Voltage 120(90~130) / 240(180~260) VAC 1 phase 2 wire DIP switch selectable
Frequency 45~65 Hz |
---|---|
Output | Voltage Max. 50 VDC @ 120 VAC input , Max. 63 VDC @ 240 VAC input
Current Continuous 2.5A, Intermittent 4A for 60 sec. Resistance Min. 25 Ohm |
Voltage Regulation | < ±1% (within 4% engine governing) |
Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
External Volts Adjustment | ±15% with 5 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 10 watt |
EMI Suppression | Internal electromagnetic interference filtering |
Thermal Drift | 0.05% per °C change in AVR ambient |
Under Frequency Protection | Knee point adjustable range 45~55 Hz |
Environment | Operating Temperature : -40~60 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz |
AVR Controls Functions | VOLTS : Voltage Adjustment
U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) DIP : 110V/220V option |
Shock | Withstands up to 20G in each X, Y, Z axes |
Dimensions | 101.0 (L) x 69.0 (W) x 22.0 (H) mm |