Deep Sea Electronics DSE7450 DC Generator Control Module
The DSE7450 DC Generator Control Module has been expertly designed to supply a load and charge the batteries on DC generators that are being used in standalone remote locations.
The module has the functionality to handle a wide range of challenging applications. Its in-built PLC editor and high number of monitoring points make it the ideal solution for all DC generator applications.
OVERALL SIZE
240 mm x 172 mm x 57 mm (9.4” x 6.8” x 2.2”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7″ x 6.3″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.92kg
Key Features and Benefits:
- Automatic/manual start with configurable start/stop timers.
- Offers flexibility to control the module manually, remotely or on pre-set timers and start/stop according to battery condition.
- Configurable inputs/outputs (10/8).
- Provides multiple installation options.
- Mains (Utility) failure detection.
- Gives full mains (utility) back up.
- AC/DC voltage measurement.
- Provides flexibility for use on AC or DC systems.
- Battery temperature monitor/charge remaining display/depth of discharge display.
- Provides information on battery temperature, charge remaining and depth of discharge.
- Backed-up real time clock.
- Ensures data is not lost when module is disconnected from its power source.
- Configurable event log (250).
- Provides access to historical alarms and operational status.
- Battery condition automatic start/stop.
- Avoids the battery draining completely by starting the generator when the battery needs charging.
- USB, RS232, RS485, Ethernet and Modbus RTU/TCP communications.
- Provides secure and simple off site monitoring. All ports are continuously active.
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 130 mA at 24 V
MAXIMUM STANDBY CURRENT
120 mA at 12 V, 65 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 150 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)