DSE 7310 MKII HTR:
-
- Heater (HTR) Version of the DSE 7310 MKII.
- Includes all the functionality of the standard DSE 7310 MKII.
- Additional Heating Control: It incorporates specific control functionality for heaters, making it ideal for applications where engine heating is required, such as in cold environments where pre-heating the engine block ensures reliable start-up.
The main distinction is that the HTR version includes integrated heater control, which adds a layer of functionality aimed at environments or scenarios where keeping the generator ready to run in cold conditions is essential.
**
SPECIFICATION
DC SUPPLY
-
Continuous Voltage Rating: 8 V to 35 V (continuous), 5 V for up to 1 minute
-
Cranking Dropouts: Survives 0 V for 100 ms if supply was ≥10 V before dropout and recovers to 5 V; no internal batteries required. LEDs and backlight do not stay on during cranking.
-
Heated Display
CURRENT CONSUMPTION
-
Maximum Operating Current: 510 mA at 12 V, 240 mA at 24 V
-
Maximum Standby Current: 330 mA at 12 V, 160 mA at 24 V
CHARGE FAIL / EXCITATION RANGE
-
0 V to 35 V
GENERATOR & MAINS (UTILITY)
-
Voltage Range:
• 15 V to 415 V AC (Phase to Neutral)
• 25 V to 719 V AC (Phase to Phase) -
Frequency Range: 3.5 Hz to 75 Hz
MAGNETIC PICKUP
-
Voltage Range: ±0.5 V to 70 V
-
Frequency Range: Up to 10,000 Hz