Specs:
Model NO. | SS321 |
---|---|
Sensing Input | Voltage 190~264 VAC 2 phase or 3 phase
Frequency 50/60 Hz selectable |
Power Input(PMG) | Voltage 170~220 VAC 3 phase 3 wire
Current 3A / phase Frequency 100~120 Hz nominal |
Output | Voltage Max. 120 VDC
Current Continuous 4A, Intermittent 7A for 60 sec. Resistance Min. 15 Ohm |
Voltage Regulation | < ±0.5% RMS (with 4% engine governing) |
Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
External Voltage Adjustment | ±10% with 5 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 18 watt |
Thermal Drift | 0.05% per °C change in AVR ambient |
Soft Start Ramp Time | 0.4~4 sec. |
Analogue Input | Max. input ±5 VDC
Sensitivity 1V for 5% generator volts Input Resistance 1 K Ohm |
Droop Input | Burden 10 Ohm
Max. Sensitivity 0.22A for 5% droop (PF=0) Max. Input 0.33A |
Under Frequency Protection
(Factory Setting) |
Set point 95% Hz
Slope 100~300% down to 30 Hz Max. Dwell 20% volts/sec. recovery |
Current Limit Input | Burden 10 Ohm
Sensitivity range 0.5~1A |
Over Voltage Detector Input | Set point 300V
Time delay 1 sec. (fixed) CB trip coil volts 10~30 VDC / 0.5 Amp |
Over Excitation Protection | Set point 120 VDC
Time delay 8~15 sec. |
Environment | Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions | VOLT : Output Voltage Adjustment
STAB : Stability Adjustment UFRO : UFRO Knee Point Set DROOP : To Set the Droop to 5% at PF=0 TRIM : To Optimize Analogue Input Sensitivity EXC : Over Excitation Trip Level Set DIP : Hz Related Voltage DIP Set DWELL : Hz Related Recovery Time Set I LIMIT : Stator Current Limit Set OVER V : Over Voltage Trip Level Set RAMP : No Load Voltage Ramp Set Time RMS : Root Mean Square of Generator |
Dimensions | 203.0 (L) x 153.0 (W) x 39.1 (H) mm |