Sensing Input | Terminal 0-110V = 95~140V
Terminal 0-220V = 170~260V Terminal 0-380V = 340~520V Frequency 50/60 Hz selectable |
---|---|
Power Input | Voltage 40~150 VAC 3 phase |
Output Current | Max. 10A |
Current Droop | Max. 4% @ P.F.=0.8 |
Voltage Regulation | < ±0.5% (with 4% engine governing) |
Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
Voltage Output | Max. 160 VDC @ 120 VAC |
External Voltage Adjustment | ±10% @ 1 K Ohm 1 watt trimmer |
Auxiliary Winding | 6~150 VAC (No load rms) |
Response Time | 0.3~1 sec. @ ±20% voltage vibration |
LAM Voltage Droop Rate | 10% & 15% selectable |
Environment | Operating Temperature : -40~60 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz |
AVR Controls Functions | VOLT : Voltage Adjustment
STAB : Stability Adjustment V/HZ : UFRO Knee Point Set EXC.MAX : Excitation Current Limit STAT : Droop Adjustment |
Dimensions | 203.0 (L) x 153.0 (W) x 60.5 (H) mm |