Operating Voltage | 10 VDC to 30 VDC |
---|---|
Output Current | From 0.5 Amp to 15 Amp |
Frequency Range | 600 Hz ~ 9500 Hz (PMG Signal) |
Idle Speed Frequency | Adjustable From 30~85% of normal |
Speed Band | ±0.25% at steady state |
Temp. Stability | Between -40~85 °C Better than ±0.5% |
Remote Speed Adjustment Range (2 mode) | Adjustable Range ±5% with 5 K Ohm potentiometer |
Ramp Time | 3 to 20 Sec. (Adjustable) |
Operation Environment | Operation Temp. : -40~85 °C
Storage Temp. : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3G @ 100~2 KHz |
DIP Switch Description | SW1 : ON Â 600~1200 Hz
SW2 : ON Â 1200~2500 Hz SW3 : ON Â 2500~5000 Hz SW4 : ON Â 5000~9500 Hz |
Governor Controls | DROOP : Droop Rate Adjustment
GAIN : MPU Output Gain Adjustment Int. : Engine Stability Adjustment RAMP-TIME : Soft Start Adjustment SPEED : Speed Adjustment IDLE : Idle Speed Adjustment |
Dimensions | 147.0 (L) x 114.0 (W) x 40.0 (H) mm |