DSE7320 MKII Auto Mains Failure Control Module For Sale
Deep Sea Electronics DSE7320 MKII Auto Mains Failure Control Module #7320-03
The DSE7320 MKII AMF control module is currently in-stock. Order yours today to take better control of your generator!
Ensure Uninterrupted Power Supply with the DSE7320 MKII Auto Mains Failure Control Module!
Experience peace of mind knowing your power systems are in capable hands with the DSE7320 MKII. This advanced control module offers:
✅ Seamless Transition: Automatically switches to backup power in the event of mains failure, keeping your operations running smoothly.
✅ Remote Monitoring: Stay informed and in control from anywhere with remote monitoring capabilities, ensuring you’re always aware of your power status.
✅ Customizable Settings: Tailor settings to your specific needs for optimal performance and efficiency.
Don’t let power outages disrupt your business. Invest in the reliability of the DSE7320 MKII control module today.
Keep your power flowing with the reliable DSE7320 MKII control module!
The DSE7320 MKII is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, gen-set applications. Monitoring an extensive number of engine parameters, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LEDs, remote PC and via SMS text alerts (with external modem). The DSE7320 MKII will also monitor the mains (utility) supply. The modules include USB, RS232 and RS485 ports as well as dedicated DSENet® terminals for system expansion.
KEY FEATURES
• Configurable power-up mode
• MPU fail delay
• Enhanced graphical user interface
• Drag & drop advanced PLC editor
• MSC ID within PLC GenComm override
• 4-Line back-lit LCD text display
• Multiple Display Languages
• Five key menu navigation
• LCD alarm indication
• Heated display option available
• Customisable power-up text and images
Frequently asked questions:
How do I reset my DSE 7320 MKII?
To reset your DSE 7320 MKII AMF controller, press the STOP/RESET and TICK buttons at the same time.
If you previously set a module security PIN, the PIN number request will be shown
SPECIFICATION
DC SUPPLY CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous 5 V for up to 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
510 mA at 12 V, 240 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
25 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)