DSE 7310 MKII HTR Auto Start Control Module
Order your DSE 7310 MKII HTR auto start control module today to take control of your generator!
DSE 7310 MKII HTR:
-
- Heater (HTR) Version of the DSE 7310 MKII.
- Includes all the functionality of the standard DSE 7310 MKII.
- Additional Heating Control: It incorporates specific control functionality for heaters, making it ideal for applications where engine heating is required, such as in cold environments where pre-heating the engine block ensures reliable start-up.
The main distinction is that the HTR version includes integrated heater control, which adds a layer of functionality aimed at environments or scenarios where keeping the generator ready to run in cold conditions is essential.
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
Heated display
MAXIMUM OPERATING CURRENT
510 mA at 12 V, 240 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
25 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)