Main features
KEY FEATURES WHEN CONNECTED TO THE COMPATIBLE MODULES
• Multiple modules (up to a maximum of 20) within the same load sharing system can be viewed • Touch-screen enabled • RS232, RS485 and Ethernet communications • Audible alarm • Front panel mounting • Protected front panel configuration • Remote monitoring • System monitoring
KEY BENEFITS
• Compatible with DSE86xx, DSE87xx & DSE88xx Load Share Modules • Data communication link allows remote system management • 800 x 480 pixel screen for high clarity
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING 8 V to 35 V continuous
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT 300 mA at 12V, 150 mA at 24V
OUTPUTS
AUXILLARY OUTPUTS C & D 2 A DC at supply voltage
DIMENSIONS
OVERALL 310 mm x 160 mm x 40 mm 12.2” x 6.3” x 1.5”
PANEL CUT-OUT 282 mm x 136 mm 11.1” x 5.3”
STORAGE TEMPERATURE RANGE -40°C to +85°C
OPERATING TEMPERATURE RANGE
Environmental Testing Standards
ELECTRO MAGNETIC COMPATIBILITY
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1 Ab/Ae Cold Test -30° C BS EN 60068-2-2 Bb/Be Dry Heat +70° C
VIBRATION
BS EN 60068-2-6 Ten sweeps in each of three major axes 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
HUMIDITY
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40° C @ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27 Three shocks in each of three major axes 15gn in 11mS
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529 IP65 – Front of module when installed into the control panel with the supplied sealing gasket.