Specs:
Model NO. | SS440 |
---|---|
Sensing Input | Voltage 190~264 VAC 1 phase 2 wire
Frequency 50/60 Hz selectable |
Output | Voltage Max. 90 VDC at 207 VAC
Current Continuous 4A, Intermittent 10A for 10 sec. Frequency Min. 15 Ohm |
Voltage Regulation | < ±1% (with 4% engine governing) |
Voltage Build-up | Residual voltage at AVR terminal > 5 VAC |
External Volts Adjustment | ±8% with 1 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 12 watt |
Thermal Drift | 0.05% per °C change in AVR ambient |
Under Frequency Protection (UFRO) | Set point 95% Hz
Slope 170% down to 30 Hz |
Soft Start Ramping | 2 sec. |
Analogue Input | Max. Input ±5 VDC
Sensitivity 1V for 5% generator volts Input Resistance 1 K Ohm |
Quadrature Droop Input | Burden 10 Ohm
Max. sensitivity 0.07A for 5% droop (PF=0) Max. input 0.33A |
Environment | Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions | VOLT : Voltage Adjustment
STAB : Stability Adjustment U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) DROOP : Droop Adjustment TRIM : Analogue Input Adjustment DIP : U/V Rate Set |
Dimensions | 150.0 (L) x 135.0 (W) x 48.0 (H) mm |