Sensing Input | Voltage 120(95~132) / 240(190~264) VAC, Â 1 phase 2 wire , jumper selectable
Frequency 50/60 Hz, jumper selectable |
---|---|
Output | Voltage Max. 90 VDC @ 207 VAC
Current Continuous 4A, Intermittent 10A for 10 sec. Resistance Min. 15 Ohm |
Voltage Regulation | < ±1.5% (with 4% engine governing) |
Voltage Build-up | Residual voltAGE at AVR terminal > 5 VAC |
Soft Start Ramp Time | 2 sec. |
External Voltage Adjustment | ±7% with 1 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 10 watt |
Thermal Drift | 0.05% per °C change in AVR ambient |
Under Frequency Protection
(UFRO) |
Set point 95% Hz
Slope 170% down to 30 Hz |
Environment | Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions | VOLT : Voltage Adjustment
STAB : Stability Adjustment UFRO : UFRO Knee Point Set |
Dimensions | 135.0 (L) x 100.0 (W) x 49.0 (H) mm |