Sensing Input | Voltage 120(90~132) / 240(171~264) VAC DIP switch selectable
Frequency 50/60 Hz , jumper selectable |
---|---|
Output | Voltage Max. 37 VDC @ 110 VAC input , Max. 73 VDC @ 220 VAC input
Current Continuous 3.5A, Intermittent 7A for 10 sec. Resistance Min. 15 Ohm Max. 100 Ohm |
Voltage Regulator Rate | < ±1% (with 4% engine governing) |
Voltage Build-up | Residual voltage at AVR terminal > 5 VAC |
External Voltage Adjustment | ±5% @ 1 K Ohm 1 watt  /  ±10% @ 2 K Ohm 1 watt |
Unit Power Dissipation | Max. 8 watt |
EMI Suppression | Internal electromagnetic interference filtering |
Under Frequency Protection
(Factory Setting) |
60 Hz system – knee point at 54 ~ 61Â Hz
50 Hz system – knee point at 45Â ~ 51Â Hz |
Environment | Operating Temperature : -40~60 °C
Storage Temperature : -65~85°C Relative Humidity : Maximum 95% Mechanical Vibration : 1.3G @ 5~26 Hz / 5.0G @ 52~1000 Hz |
AVR Controls Functions | VOLT Voltage : Adjustment
STAB : Stability Adjustment U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) |
Dimensions | 99.5 (L) x 67.0 (W) x 47.5 (H) mm |