Sensing & Power Input | Voltage 160~260 VAC 1 phase 2 wire
Frequency 50/60 Hz selectable |
---|---|
Output | Voltage Max. 170 VDC @ 240 VAC input
Current Continuous 5A, Intermittent 7A for 10 sec. Resistance Min. 15 Ohm Max. 100 Ohm |
Voltage Regulation | < ±1% (with 4% engine governing) |
Voltage Build-up | Residual voltage at AVR terminal > 5 VAC |
External Volts Adjustment | ±10% with 5 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 8 watt |
Soft Start Ramp Time | 2 sec. |
Thermal Drift | 0.03% per °C change in AVR ambient |
Under Frequency Protection | For 60 Hz -knee point set at 55 Hz
For 50 Hz- knee point set at 45 Hz |
Environment | Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Function | VOLTS : Voltage Adjustment
STAB : Stability Adjustment U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) |
Dimensions | 150.0 (L) x 100.0 (W) x 74.0 (H) mm |
Weight | 421 g ±2% |