Sensing Input | Voltage 220 VAC 1 phase 2 wire
Frequency 50/60 Hz select by jumper |
---|---|
Power Input | Voltage 10~26 VDC |
Output | Current 20 mili-Amps |
Volts Regulation | < ±1% (with 4% engine governing) |
External Volts Adjustment | ±10% with 1 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 2 watt |
Thermal Drift | 0.05% per °C change in AVR ambient |
Under Frequency Protection
(Factory Setting) |
60 Hz system presets knee point at 55 Hz
50 Hz system presets knee point at 45 Hz |
Environment | Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
AVR Controls Functions | STAB : Stability Adjustment |
Dimensions | 127.2 (L) x 141.5 (W) x 39.0 (H) mm |
Weight | 109 g ±2% |