| Sensing Input | Voltage 220 VAC 1 phase 2 wire
Frequency 50/60 Hz select by jumper |
|---|---|
| Power Input | Voltage 10~26 VDC |
| Output | Current 20 mili-Amps |
| Volts Regulation | < ±1% (with 4% engine governing) |
| External Volts Adjustment | ±10% with 1 K Ohm 1 watt trimmer |
| Unit Power Dissipation | Max. 2 watt |
| Thermal Drift | 0.05% per °C change in AVR ambient |
| Under Frequency Protection
(Factory Setting) |
60 Hz system presets knee point at 55 Hz
50 Hz system presets knee point at 45 Hz |
| Environment | Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
| AVR Controls Functions | STAB : Stability Adjustment |
| Dimensions | 127.2 (L) x 141.5 (W) x 39.0 (H) mm |
| Weight | 109 g ±2% |