Sensing Input | Terminal 1,2 Â 3,4 Â 5,6
Can be connected to Y or ? 220~480 VAC single phase / three phase 50/60 Hz |
---|---|
Power Input | 50~280 VAC (1,2) 50/60 Hz |
Output | Voltage 63 VDC @ 220 VAC Input
Current Continuous 6A Max. Intermittent 7A for 10 sec. |
Voltage Regulation | < ±1% (with 4% engine governing) |
Voltage Build-up | Residual Voltage above 5 VAC 25 Hz |
External Volts Adjustment | 100 K Ohm 1/2 watt ±5% |
Unit Power Dissipation | Max. 5 watt |
EMI Suppression | Internal Electromagnetic Interference Filtering |
Under Frequency Protection | Adjustable range 42~62 Hz |
Excitation Winding Resistance | DC Resistance 10~100 Ohm |
Over Excitation Protection | 25~55 VDC @ 0.1~20 sec. |
Environment | Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz |
AVR Controls Function | VOLTS : Voltage Adjustment
STAB : Stability Adjustment U/F : Under Frequency Protection AMP : Over Excitation Setting |
Dimensions | 150.0 (L) x 114.7 (W) x 35.2 (H) mm |
Weight | 520 g ±2% |