Input | Voltage 120(90~140) VAC 1 phase 2 wire
Frequency 45~65 Hz |
---|---|
Output | Voltage Max. 100 VDC @ 120 VAC input
Current Continuous 8A, Intermittent 10A for 10 sec. Resistance Min. 15 Ohm |
Voltage Regulation | < ±1% (with 4% engine governing) |
Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
External Volts Adjustment | ±5% with 5 K Ohm 1/2 watt trimmer |
Unit Power Dissipation | Max. 6 watt |
Thermal Drift | 0.03% per °C change in AVR ambient |
EMI Suppression | Internal electromagnetic interference filtering |
Under Frequency Protection | Knee point 47/57 Hz (Adjustable) |
Environment | Operating Temperature : -40~60 °C
Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz |
AVR Controls Functions | VOLT : Voltage Adjustment
STAB : Stability Adjustment U/F*: To Set the U/F Knee Point (*U/F: Under Frequency Protection) |
Shock | Withstands up to 20G in each X, Y, Z axes |
Dimensions | 140.0 (L) x 75.0 (W) x 51.0 (H) mm |
Weight | 310 g ±2% |