DSE4610 Auto Start Control Module For Sale
The DSE4610 is a compact Auto Start Control Module that has been developed to provide an outstanding range of features within a compact enclosure.
OVERALL SIZE
140 mm x 113 mm x 43 mm (5.5” x 4.4” x 1.5”)
PANEL CUTOUT SIZE
118 mm x 92 mm (4.6″ x 3.6″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.28kg
KEY Features and Benefits
- Large back-lit icon LCD display.
- Displays information to the operator in a clear and concise format.
- 3-phase generator sensing.
- Provides true generator sensing.
- 600 V ph-ph nominal system compatibility.
- Provides global flexibility.
- Generator & load power monitoring (kW, kV A, kV Ar, pf).
- Provides clear accurate power measurement information.
- Generator overload protection (kW).
- Provides engine overload protection.
- Configurable inputs & outputs.
- Provides multiple installation options.
- Configurable DC, volt-free and staged loading outputs.
- Provides multiple installation options.
- Fuel & crank outputs.
- Provides controlled engine starting and stopping.
- Magnetic pick-up speed sensing.
- Provides full monitoring flexibility.
- Engine speed protection, engine hours counter, engine pre-heat, engine run-time scheduler, engine idle control for start/stop.
- Ensures the engine is fully monitored for improved operating performance.
- Battery voltage monitoring.
- Ensures the battery maintains enough power at all times.
- Configurable event log (50).
- Provides access to historical alarms and operational status.
- DSE Configuration Suite PC Software.
- Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 to 719 V AC (Ph – Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)